Home › Calculators › Voltage Drop Calculator

Voltage Drop Calculator

Calculate voltage drop in volts and percent for copper or aluminum wire on single-phase, DC or three-phase circuits, check it against the NEC 3% and 5% recommendations, find the smallest wire that passes, and see the AWG gauge wiring chart.

Updated November 4, 2026. Free, no sign-up; everything runs in your browser and nothing you type is stored.

Voltage drop calculator

Voltage drop
–
–Percent drop
–Voltage at the load
–Check
–Smallest wire within the limit

Voltage drop formula

Single-phase or DC: VD = 2 × L × I × R ÷ 1,000; three-phase: VD = 1.732 × L × I × R ÷ 1,000, where L is the one-way length in feet, I the current in amps and R the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8, at 75 °C). 10 AWG copper (1.24 Ω/kft) carrying 20 A over 100 ft on 120 V drops 2 × 100 × 20 × 1.24 ÷ 1,000 = 4.96 V (4.13%); 8 AWG drops 3.11 V (2.59%).

The NEC's informational notes recommend no more than 3% drop on a branch circuit and 5% combined for feeder plus branch circuit. It's a recommendation for efficiency and equipment performance, not a mandatory rule (sensitive electronic equipment and fire pumps have specific requirements). This DC-resistance method is accurate for small wires; for large AC conductors, NEC Table 9 (effective impedance) gives slightly different results.

Gauge wiring chart: ampacity and resistance

SizeCopper 60 °C (A)Copper 75 °CCopper 90 °CCopper Ω/kftAluminum Ω/kft
14 AWG1520253.145.17
12 AWG2025301.983.25
10 AWG3035401.242.04
8 AWG4050550.7781.28
6 AWG5565750.4910.808
4 AWG7085950.3080.508
3 AWG851001150.2450.403
2 AWG951151300.1940.319
1 AWG1101301450.1540.253
1/0 AWG1251501700.1220.201
2/0 AWG1451751950.09670.159
3/0 AWG1652002250.07660.126
4/0 AWG1952302600.06080.1
250 kcmil2152552900.05150.0847
300 kcmil2402853200.04290.0707
350 kcmil2603103500.03670.0605
400 kcmil2803353800.03210.0529
500 kcmil3203804300.02580.0424

Ampacity: NEC Table 310.16 (not more than three current-carrying conductors, 30 °C ambient). Small conductors are limited by 240.4(D): 14 AWG copper to 15 A, 12 AWG to 20 A, 10 AWG to 30 A. Most residential terminations are rated 60 °C or 75 °C; size to the lowest rating in the circuit. Resistance: NEC Chapter 9 Table 8, stranded, uncoated copper and aluminum at 75 °C.

Common questions

How do I calculate voltage drop?

VD = 2 × length × current × resistance per 1,000 ft ÷ 1,000 (single-phase). 10 AWG, 20 A, 100 ft: 4.96 V.

What is the maximum voltage drop allowed?

The NEC recommends 3% on a branch circuit and 5% total; it's a recommendation, not a requirement.

What size wire for 20 amps at 100 feet?

10 AWG copper drops 4.1% on 120 V; 8 AWG keeps it under 3%.

How many amps can 12 gauge wire carry?

20 A for 12 AWG copper (240.4(D) limit), though Table 310.16 lists 25 A at 75 °C.

Does three-phase have less voltage drop?

Yes: the factor is 1.732 instead of 2 for the same current and length.