Enter the number and size of THHN/THWN-2 conductors (mixed sizes allowed) to see the fill percentage in EMT, PVC Schedule 40 or PVC Schedule 80, whether it passes the NEC 53/31/40% rule, and the smallest conduit size that works.

Updated November 4, 2026. Free, no sign-up; everything runs in your browser and nothing you type is stored.

Conduit fill calculator

Conductors (THHN / THWN-2, including grounds):

SizeQuantity
–Fill rule
–Total conductor area
–Fill in chosen conduit
–Smallest conduit that works

Conduit sizes

NEC conduit fill rules

NEC Chapter 9, Table 1 limits how much of a conduit's cross-section the conductors may fill: 53% for one conductor, 31% for two, and 40% for three or more. Add up each conductor's area from Chapter 9, Table 5, and compare it with the conduit's allowed area from Table 4. Equipment grounding conductors count.

Example: six 12 AWG THHN (0.0133 in² each) and one 10 AWG ground (0.0211) total 0.1009 in². ¾" EMT allows 40% × 0.533 = 0.213 in², so it fits at 18.9% fill.

Common questions

What is the 40% conduit fill rule?

With three or more conductors, their total cross-sectional area can't exceed 40% of the conduit's internal area (NEC Chapter 9, Table 1).

How many 12 AWG wires fit in 1/2-inch EMT?

9 THHN conductors: 0.122 in² allowed ÷ 0.0133 in² each = 9.2.

How many 12 AWG wires fit in 3/4-inch EMT?

16 THHN: 0.213 ÷ 0.0133 = 16.0.

Do ground wires count toward conduit fill?

Yes, equipment grounding and bonding conductors count toward fill.

Why is the limit 31% for two wires?

With two conductors there's a higher risk of jamming during the pull, so the NEC allows less fill than for one or three or more.